Wire Size Calculator
Calculate the correct electrical wire gauge for any circuit. Enter load current, voltage, cable length, and conductor material to get the right wire size with voltage drop analysis.
Wire Size Calculator
Calculate the correct electrical wire gauge based on current, voltage, distance, and material. Includes voltage drop analysis and safety recommendations.
Actions
Circuit Parameters
One-way distance from source to load
Common Applications
Wire Size Reference Table
| mm² | Copper (A) | Aluminum (A) |
|---|---|---|
| 1.0 | 10 | - |
| 1.5 | 15 | 12 |
| 2.5 | 21 | 16 |
| 4 | 28 | 22 |
| 6 | 36 | 28 |
| 10 | 50 | 39 |
| 16 | 68 | 53 |
| 25 | 89 | 69 |
| 35 | 110 | 85 |
| 50 | 134 | 104 |
Typical IEC cable ratings for a few loaded conductors at 30 °C ambient. Check IEC 60364-5-52 or local rules for your installation method.
Next step
Related tools
What Is a Wire Size Calculator?
A wire size calculator is a free electrical tool that determines the correct cable size for any circuit based on load current, supply voltage, cable run length, conductor material, and maximum allowable voltage drop. It answers the most common question in electrical installation: what gauge wire do I need for this circuit?
Selecting the wrong size has real consequences. Undersized wire overheats under load — causing insulation degradation, nuisance tripping, fire risk, and failed inspections. Oversized wire wastes material cost and makes terminations harder. The correct size satisfies two independent constraints at once: ampacity (current-carrying capacity without overheating) and voltage drop (keeping the supply voltage within usable range at the load end).
This cable size calculator is built for licensed electricians sizing branch circuits and feeders, electrical engineers designing building power systems, solar installers running AC wiring, DIY homeowners planning permitted work, and students studying NEC or IEC cable sizing. Results are given in mm² (IEC cable sizes) or AWG (US sizes, rated to the NEC), with single-phase and three-phase support. Free, no signup required.
How Wire Size Calculation Works
Core Formulas
VD (1-phase) = 2 × L × I × R ÷ 1000
VD (3-phase) = √3 × L × I × R ÷ 1000
VD% = VD ÷ Vsupply × 100
L = one-way length (m) · I = current (A) · R = conductor resistance (Ω/km) · V = supply voltage
- Ampacity check: every wire size has a maximum current rating — the calculator selects only sizes rated above the load current
- Voltage drop check: the calculator then tests each candidate size against the voltage drop formula and selects the smallest one that keeps VD% below your limit
- Copper resistivity: ≈ 0.0172 Ω·mm²/m at 20°C — rising to ~0.0206 at 75°C operating temperature
- Aluminum resistivity: ≈ 0.0282 Ω·mm²/m at 20°C — approximately 1.64× copper, requiring larger cross-section for identical performance
- Three-phase advantage: the √3 (≈ 1.732) factor vs 2× for single-phase means three-phase circuits need less conductor for the same power and distance
How to Use the Wire Size Calculator
Step-by-Step Guide
- 1Enter Load Current: Type the full-load current in amperes. For motor circuits, use the nameplate FLA rating multiplied by 1.25. For general circuits, use the breaker amperage. Always size for the maximum expected load.
- 2Set Voltage and System Type: Select your supply voltage and choose single-phase or three-phase. Three-phase systems use the square root of 3 factor in the voltage drop formula, reducing conductor requirements for the same power.
- 3Enter Cable Length: Enter the one-way distance from the power source to the load in meters. The formula accounts for both conductors automatically — do not double the distance manually.
- 4Choose Conductor Material: Select copper or aluminum. Copper offers higher ampacity per mm² and easier termination. Aluminum requires a larger cross-section for the same current but is cost-effective for long feeder runs.
- 5Set Maximum Voltage Drop: Enter your allowable voltage drop percentage. Use 3% for NEC branch circuits, 2% for feeders, and 1 to 2% for sensitive equipment. The calculator finds the smallest wire satisfying both ampacity and voltage drop.
- 6Read and Apply the Result: The calculator returns the recommended wire size in mm² or AWG (switch with the unit buttons), actual voltage drop percentage, power loss in watts, and a conservative next-size-up alternative. Export the result for project documentation.
What This Tool Provides
- ✓Recommended wire size in mm² or AWG
- ✓Actual voltage drop at selected size
- ✓Voltage drop percentage vs your limit
- ✓Power loss in watts for the cable run
- ✓Next-size-up conservative alternative
- ✓Single-phase and three-phase support
- ✓Copper and aluminum conductor options
- ✓Supply voltages from 110 V to 415 V
- ✓Calculation history (last 10 entries)
- ✓Export results as text report
- ✓Copy result to clipboard
- ✓Private: your inputs are not collected or stored
- ✓No registration required
Real-World Use Cases
Residential Kitchen Circuit
A homeowner is adding a dedicated 20-amp, 120V circuit for a countertop microwave in a kitchen 18 meters (59 ft) from the main panel. They enter 20A, 120V, 18m, copper, single-phase, 3% max drop, AWG. 12 AWG is the smallest size allowed on a 20A circuit, but over this run it would drop more than 3%, so the calculator returns 10 AWG with a 2.4% drop. Had the run been 30 meters, it would step up to 8 AWG (2.6%).
Three-Phase Motor Feed
An electrician is wiring a 15-amp conveyor motor 45 meters from the motor control center. Fed single-phase at 230V, the run needs 4 mm² copper (2.7% drop). Fed three-phase at 400V, the same current and distance need only 2.5 mm² (2.2% drop), because the line voltage is higher and the √3 factor replaces the factor of 2.
Workshop Radial Circuit
A 32-amp radial circuit feeds a workshop 30 meters from the consumer unit at 230V. With copper cable and a 3% limit, the calculator returns 6 mm² with a 2.6% drop. A smaller cable could carry the current, but the length decides the size.
Subpanel Feeder Sizing
A contractor is running a 60-amp feeder from a main panel to a detached garage subpanel 40 meters (131 ft) away, 240V single-phase, with a 2% feeder limit. In AWG, the calculator returns 1 AWG aluminum (1.7% drop) or 3 AWG copper (1.6%). The installer checks that both panels have aluminum-rated lugs and uses anti-oxidant compound before choosing the aluminum cable.
EV Charger Installation
A homeowner is installing a 48-amp Level 2 EV charger in a garage 22 meters (72 ft) from the main panel. The NEC treats EV charging as a continuous load, so the circuit is sized at 125%: 48 × 1.25 = 60A. Entering 60A, 240V, 22m, copper, single-phase, 3% and AWG gives 6 AWG with a 1.8% drop, for a 60A breaker.
Commercial Lighting Circuit
An engineer is sizing the branch circuit for a 10A LED lighting load in a warehouse at 230V. With fixtures 45 meters from the panel, 2.5 mm² copper keeps the drop at 2.9%. At 55 meters the calculator steps up to 4 mm² (2.2%), so the engineer weighs a closer panel against the larger cable.
Tips & Common Mistakes
Pro Tips
- 💡For motor circuits, multiply the nameplate FLA by 1.25 before entering it into the calculator. NEC 430.22 requires branch circuit conductors to be rated at 125% of the motor's full-load current for continuous-duty motors — not 100%. A 10A motor needs a 12.5A conductor rating minimum.
- 💡Always use the one-way distance to the load, not the total round-trip length. The voltage drop formula already accounts for both conductors (the factor of 2 in single-phase calculations). Entering the round-trip distance doubles the result and will oversize your wire unnecessarily.
- 💡If the calculator recommends a size larger than you expected, check whether switching from single-phase to three-phase power is feasible. The √3 factor in three-phase circuits reduces voltage drop for the same conductor, often allowing you to drop one or two wire sizes on long runs to motors.
- 💡For cable runs buried directly in the ground or pulled through conduit with more than three current-carrying conductors, derate the ampacity. NEC Table 310.15(B)(3)(a) requires 80% capacity for four cables, 70% for five or six, 50% for seven to nine. Multiply your actual current by the inverse of the derating factor before entering it — this gives the effective ampacity the wire must supply.
- 💡Size for future load growth when possible. Running an extra wire size larger (e.g., 4 mm² instead of 2.5 mm²) on a long home run costs relatively little in material versus the labor cost of pulling new wire later. This is especially true for sub-panel feeders and service entrance conductors.
- 💡Verify that your selected wire size is compatible with the breaker. Under NEC 240.4(D), copper 14 AWG may be protected at no more than 15A, 12 AWG at 20A and 10 AWG at 30A. Putting 14 AWG on a 20A breaker is a code violation even if the run is short.
Common Mistakes to Avoid
- ✕Don't size wire for ampacity alone and ignore voltage drop. A 20A circuit at 120V over 50 meters (164 ft) has enough ampacity with 12 AWG copper, but the voltage drop is about 10.8%, more than three times the 3% guideline. Lights dim, motor torque drops and equipment may fault. Always check voltage drop on longer runs.
- ✕Don't use the 'rule of thumb' AWG shortcuts without checking your specific voltage and distance. Common shortcuts assume 120V, 30°C, and short runs. At 48V DC or 24V control circuits, the same current over the same distance produces far higher percentage voltage drops — the rule of thumb breaks down entirely.
- ✕Don't forget that aluminum requires anti-oxidation compound and aluminum-rated lugs at every termination point. Aluminum conductors form an oxide layer that increases contact resistance over time. Without proper compound and connectors, the connection heats up, and the insulation eventually fails — a documented cause of residential fires.
- ✕Don't assume the same wire size works for both the hot and neutral conductors in a multi-wire branch circuit. A shared neutral serving two 20A ungrounded conductors on opposite phases carries up to 20A of unbalanced current. The neutral must be sized identically to the hots — it is not a 'lighter' conductor just because it doesn't carry current under balanced load.
- ✕Don't size wire for the continuous load without applying the 125% continuous load factor where required. NEC 210.19 requires branch circuit conductors to be sized at 125% of the continuous load (a load expected to operate for 3 or more hours). Failing to apply this factor means the wire runs at 100% of its thermal rating continuously — shortening insulation life significantly.
Wire Size Reference Table — AWG / mm² by Ampacity and Distance
AWG Sizes Used by the Calculator (US, NEC)
| AWG | Area (mm²) | Copper (A) | Aluminum (A) | Copper resistance (Ω/km) |
|---|---|---|---|---|
| 14 | 2.08 | 15 | — | 10.30 |
| 12 | 3.31 | 20 | 15 | 6.50 |
| 10 | 5.26 | 30 | 25 | 4.07 |
| 8 | 8.37 | 50 | 40 | 2.55 |
| 6 | 13.3 | 65 | 50 | 1.61 |
| 4 | 21.2 | 85 | 65 | 1.01 |
| 3 | 26.7 | 100 | 75 | 0.80 |
| 2 | 33.6 | 115 | 90 | 0.64 |
| 1 | 42.4 | 130 | 100 | 0.51 |
| 1/0 | 53.5 | 150 | 120 | 0.40 |
| 2/0 | 67.4 | 175 | 135 | 0.32 |
| 3/0 | 85.0 | 200 | 155 | 0.25 |
* Ampacity from NEC Table 310.16, 75°C column, 30°C ambient, limited by NEC 240.4(D) for 14–10 AWG. Resistance from NEC Chapter 9, Table 8 (stranded, 75°C). Derate for bundling, high ambient temperature or burial.
Maximum One-Way Run Length (Copper, 240V Single-Phase, 3% VD Limit)
| Wire Size | 15A Circuit | 20A Circuit | 30A Circuit | 50A Circuit |
|---|---|---|---|---|
| 14 AWG | 23 m (76 ft) | — | — | — |
| 12 AWG | 37 m (121 ft) | 28 m (91 ft) | — | — |
| 10 AWG | 59 m (194 ft) | 44 m (145 ft) | 29 m (97 ft) | — |
| 8 AWG | 94 m (308 ft) | 71 m (231 ft) | 47 m (154 ft) | 28 m (93 ft) |
| 6 AWG | 149 m (489 ft) | 112 m (367 ft) | 74 m (244 ft) | 45 m (147 ft) |
| 4 AWG | 238 m (779 ft) | 178 m (584 ft) | 119 m (390 ft) | 71 m (234 ft) |
* Longest one-way run within a 3% voltage drop at 240V single-phase, copper at 75°C, the same figures the calculator uses. Dashes mean the size is not rated for that current.
Frequently Asked Questions
What is a wire size calculator?
A wire size calculator determines the correct electrical conductor size for a given load based on current, voltage, cable length, and conductor material. It checks two constraints simultaneously: ampacity (the wire must carry the required current without overheating) and voltage drop (the supply voltage must stay within acceptable limits at the load end — typically within 3% for branch circuits).
How is wire size calculated?
Wire sizing uses two parallel calculations. Ampacity sets the minimum size the wire must be rated to carry the load current. Voltage drop is calculated as VD = 2 × L × I × R / 1000 for single-phase, or VD = 1.732 × L × I × R / 1000 for three-phase, where L is length in meters, I is current in amperes, and R is conductor resistance in ohms per kilometer. The calculator selects the smallest size that satisfies both constraints.
What wire size do I need for a 20-amp circuit?
In the US, a 20-amp circuit needs at least 12 AWG copper (NEC 240.4(D)). At 120V with a 3% voltage drop limit, 12 AWG reaches about 13 meters (45 feet); beyond that the calculator steps up to 10 AWG (to about 22 m / 72 ft) and then 8 AWG (to about 35 m / 115 ft). On a 230V metric installation, 2.5 mm² copper covers a 20A circuit up to about 23 meters at 3%. Enter your actual length for your run.
What is the difference between AWG and mm²?
AWG (American Wire Gauge) is the North American sizing system where smaller numbers indicate larger conductors — 10 AWG is larger than 14 AWG. mm² (square millimeters) is the metric IEC system used internationally, directly expressing the conductor cross-sectional area. 14 AWG is 2.08 mm², 12 AWG is 3.31 mm², 10 AWG is 5.26 mm² and 8 AWG is 8.37 mm², so the nearest larger metric sizes are 2.5, 4, 6 and 10 mm². The two systems are not swapped one-for-one; the calculator uses each system's own ratings.
Should I use copper or aluminum wire?
Copper is preferred for most residential and commercial wiring because it has better conductivity, higher ampacity per mm², and easier termination at standard lugs. Aluminum is lighter and cheaper per meter, making it cost-effective for large feeders and utility runs. Aluminum requires approximately 1.5 times the cross-section of copper for the same ampacity, and connections must use anti-oxidation compound with aluminum-rated connectors.
What is an acceptable voltage drop percentage?
NEC and IEC guidelines recommend a maximum 3% voltage drop for branch circuits and 2% for feeder circuits, with a combined total of no more than 5%. Sensitive equipment like computers, medical devices, and precision instruments should use 1 to 2% as their maximum. Exceeding 5% total can cause equipment malfunction, motor overheating, and reduced operating efficiency.
How do I measure cable length for the calculator?
Measure the one-way distance from the power source to the load — for example, from the breaker panel to the outlet or motor. Do not double it. The voltage drop formula for single-phase already multiplies by 2 to account for both conductors. For conduit runs with bends, add 10 to 15 percent extra to account for the actual routed path length.
Why does the calculator recommend a larger wire than I expected?
Long cable runs are the most common reason. A 15-amp circuit at 120V over 60 meters needs 6 AWG (10 mm² in metric), four sizes larger than ampacity alone would allow, because voltage drop forces the upgrade. Other factors that push toward larger conductors include low supply voltage, aluminum instead of copper, stricter voltage drop limits for sensitive loads, and three-phase versus single-phase system type.
Does the calculator account for temperature derating?
This calculator uses standard ampacity values for typical installation conditions: 30°C ambient temperature and limited conductor bundling. For high-temperature environments, multiple cables in the same conduit, or cables buried directly in the ground, apply the NEC Table 310.15 or IEC 60364 derating factors to your current before entering it. Multiply your load current by the inverse of the derating factor to get the adjusted input value.
Is my data private when using this calculator?
Yes. We do not collect or store what you enter.
Who Uses This Wire Size Calculator?
Licensed Electricians
Size branch circuits, feeders, and service conductors quickly on the job site. Verify that voltage drop stays within NEC or IEC limits before pulling wire on long commercial runs.
Electrical Engineers
Design building power distribution systems, spec panel schedules, and confirm conductor sizing for motor circuits, lighting panels, and sub-panels during engineering review.
Solar Installers
Size the AC cable from the inverter to the main panel, where a long run to a ground-mounted array can push voltage drop past the limit.
Homeowners & DIYers
Plan permitted electrical work — adding a sub-panel to a garage, wiring an EV charger, or running a dedicated circuit for a hot tub — with confidence before buying materials.
Electrical Students
Work through NEC and IEC cable sizing exercises, verify textbook examples, and develop intuition for how current, distance, and voltage interact in conductor selection.
Maintenance Technicians
Evaluate existing wiring on equipment upgrades, check whether current conductors can handle a load increase, and document conductor sizes and voltage drops for maintenance records.
Related Tools
Voltage Drop Calculator
Calculate voltage drop in wires.
Cable Length Calculator
Determine required cable length.
Fuse Rating Calculator
Calculate proper fuse rating.
Circuit Breaker Calculator
Determine breaker size for circuits.
House Wiring Load Calculator
Estimate total electrical load in a house.
Earthing Resistance Calculator
Compute grounding resistance.
Energy Consumption Calculator
Calculate energy usage in kWh.
Generator Size Calculator
Determine generator size needed.
Room Lighting Calculator
Calculate number of lights needed.
Fan Power Consumption Calculator
Estimate power used by fans.
Air Conditioner Power Calculator
Calculate AC unit power usage.
Solar Panel Calculator
Estimate solar panel requirements.